CAVO BUS PER ALIMENTAZIONE, IMPIEGO: Cavi per alimentazione, controllo, audio e dati |
BUS-CABLE FOR POWER, STANDARD USE: Cables for power, control, audio and data |
||
|
|
|||
|
CARATTERISTICHE TECNICHE |
TECHNICAL FEATURES |
||
|
CONDUTTORI: Flessibili in rame stagnato sec. CEI 20-29 cl.5 (IEC 228), VDE 0295 cl.5 |
![]() |
CONDUCTORS: Stranded tinned copper conductors CEI 20-29 cl.5 (IEC 228), VDE 0295 cl.5 ref. |
|
|
ISOLANTE: Polivinilcloruro (PVC) esente Piombo sec. CEI 20-20 Cl. R2 |
![]() |
INSULATION: Polyvinylchloride (PVC) lead free CEI 20-20 Cl. R2 Ref. |
|
|
SCHERMATURA: Coppie dati: nastro di Alluminio/poliestere con conduttore di continuità in rame stagnato |
|
ASSEMBLING: Polyester tape helically wound |
|
|
SEPARATORE: Nastro di poliestere |
|
ASSEMBLING: Polyester tape helically wound |
|
|
GUAINA ESTERNA: Polivinilcloruro (PVC) colore: blu (diverso a richiesta) |
|
JACKET: Polyvinylchloride (PVC) colour: blue or on request |
|
|
RESISTENZA ELETTRICA DEI CONDUTTORI: 0.25 mm2 : <78 Ohm/Km 0.50 mm2 : <39 Ohm/Km 1.5 mm2 : <13,7 Ohm/Km |
![]() |
ELECTRICAL CONDUCTOR RESISTANCE: 0.25 mm2 : <78 Ohm/Km 0.50 mm2 : <39 Ohm/Km 1.5 mm2 : <13,7 Ohm/Km |
|
|
TEMPERATURA DI ESERCIZIO: -15°C + 80°C |
![]() |
WORKING TEMPERATURE: -15°C + 80°C |
|
|
RAGGIO DI CURVATURA: 15 volte il diametro del cavo |
![]() |
BENDING RADIUS: 15 times overall diameter of cable |
|
|
TENSIONE DI ESERCIZIO: Alimentazione: 300 V Dati: 50 V |
![]() |
WORKING VOLTAGE: Voltage: 300 V Data: 50 V |
|
|
TENSIONE DI PROVA: 1500 V |
![]() |
TEST VOLTAGE: 1500 V |
|
|
PROVA N.P. FIAMMA: Standard: sec. CEI 20-22 II (IEC 332.3A) |
![]() |
FLAME RETARDANT TEST: Standard: CEI 20-22 II (IEC 332.3A) Ref. |
|
|
IMPEDENZA DI TRASFERIMENTO: max 200 mohm/m (f<10MHz) |
![]() |
SURFACE TRANSFER IMPEDANCE: max 200 mohm/m (f<10MHz) |
|
|
CAPACITA’ DI LAVORO: Coppie dati: < 170 pF/m |
![]() |
CAPACITANCE: Data twist pairs: < 170 pF/m |
|
|
I SUDDETTI CAVI POSSONO ESSERE FORNITI IN VERSIONE LSZH ESENTI DA ALOGENI E COPPIE DATI A BASSA CAPACITA’ |
THE ABOVE MENTIONED CABLES CAN BE SUPPLIED LSZH HALOGEN FREE AND LOW CAPACITANCE DATA TWIST PAIRS |
||
Download technical features and cable's typology
(PDF)![]()