CAVI BUS A COPPIE SCHERMATI IMPIEGO: Cavi per sistemi bus per il controllo intelligente di |
TWISTED PAIR FOIL-SHIELDED BUS CABLES STANDARD USE: Bus-signal cables for the intelligent system control in |
||
|
|
|||
|
CARATTERISTICHE TECNICHE |
TECHNICAL FEATURES |
||
|
CONDUTTORI: Rame rosso a filo unico diametro 0.80 mm (sezione nominale 0.50 mm2 - 20AWG) |
![]() |
CONDUCTORS: Solid bare copper diameter 0.80 mm (nominal cross sect. area 0.50 mm2 - 20AWG) |
|
|
ISOLANTE: Polivinilcloruro (PVC) esente Piombo sec. CEI 20-20 Cl. R2 |
![]() |
INSULATION: Polyvinylchloride (PVC) lead free CEI 20-20 Cl. R2 Ref. |
|
|
SCHERMATURA: Nastro di Alluminio/poliestere con conduttore di continuità in rame rosso a filo unico diametro 0,80 mm |
|
SHIELD: Aluminium/polyester tape helically wound, solid bare copper drain wire 0,80 mm diameter |
|
|
GUAINA ESTERNA: Polivinilcloruro (PVC) esente Piombo colore: verde |
|
JACKET: Polyvinylchloride (PVC) lead free colour: green |
|
|
RESISTENZA ELETTRICA DEI CONDUTTORI: < 37.5 Ohm/Km |
![]() |
ELECTRICAL CONDUCTOR RESISTANCE: < 37.5 Ohm/Km |
|
|
TEMPERATURA DI ESERCIZIO: -15°C + 80°C |
![]() |
WORKING TEMPERATURE: -15°C + 80°C |
|
|
TENSIONE DI ESERCIZIO: 50 V |
![]() |
WORKING VOLTAGE: 50 V |
|
|
TENSIONE DI PROVA: 800 V |
![]() |
TEST VOLTAGE: 800 V |
|
|
PROVA N.P. FIAMMA: Standard: sec. CEI 20-35 (IEC 332.1) A richiesta: sec. CEI 20-22 II (IEC 332.3A) |
![]() |
FLAME RETARDANT TEST: Standard: CEI 20-35 (IEC 332.1) Ref. On request: CEI 20-22 II (IEC 332.3A) Ref. |
|
|
IMPEDENZA DI TRASFERIMENTO: max 200 mohm/m (f<10MHz) |
![]() |
SURFACE TRANSFER IMPEDANCE: max 200 mohm/m (f<10MHz) |
|
|
CAPACITA’ DI LAVORO: Coppie dati: < 100 pF/m |
![]() |
CAPACITANCE: Data twist pairs: < 100 pF/m |
|
|
I SUDDETTI CAVI POSSONO ESSERE FORNITI IN VERSIONE FLESSIBILE ED IN VERSIONE LSZH ESENTI DA ALOGENI |
THE ABOVE MENTIONED CABLES CAN BE SUPPLIED WITH FLEXIBLE STRANDED CONDUCTORS AND LSZH HALOGEN FREE |
||
Download technical features and cable's typology
(PDF)![]()