STANDARD USE: Twisted pairs shielded cables for interconnection of industrial electronic appliances in embedded systems; outstanding resistance to industrial oils and other chemical and mechanical agents, UL-CSA approval.

Technical Features

  • Conductors Flexible stranded bare or tinned copper (Cu-ETP1) UL 1581, VDE 0295 cl.5 ref.
  • Insulation Polyolefin
    Twisted pair colour code: DIN 47100 ref.
  • Optional First Shield Aluminium/polyester tape with aluminium side in direct contact with braid
  • Overall Shield Tinned copper braid with stranded tinned copper drain wire. Optical coverage: ≥ 85%
  • Optional Assembling Non woven tape.
  • Jacket Low friction halogen free matt flame retardant Polyurethane, hydrolysis, microbial attack, abrasion, tear, oil resistant
    UL 1581 ref.
    Colour code: Violet Ral 4001
  • Electrical Conductor Resistance 22AWG: < 59,4 Ohm/Km
    21AWG: < 43,6 Ohm/Km
  • Pair Capacitance 50 pF/m
  • Characteristic Impedance 120 Ohm
  • Transmission Rate 1000 Kbit/s: fino a 40 m
    500 Kbit/s: fino a 300 m
    100 Kbit/s: fino a 600 m
    50 Kbit/s: fino a 1000 m
  • Operating Voltage 30 V
  • Operating Temperature -30°C +80°C
  • Bending radius 6 times overall diameter of cable.
  • Flame retardant test; Non-Halogen Verification CEI 20-35/1-2, EN 60332-1-2, IEC 60332-1-2 UL 1581 cable flame test, FT1 test. < 0,5 % (CEI 20-37/2-1, CEI EN 50267-2-1, IEC 60754-1)
  • UL-CSA Approval (E235078) AWM Style 20236 80°C 30 V – CSA I/II A/B 80°C 30 V FT1 AWM Style 20554 80°C 30 V - CSA I/II A/B 80°C 30 V FT1