Elettronica Conduttori - Cavi elettrici speciali

ISO/TS certified company

<

Multicore fire resistant, halogen free (LSZH) FTE4OM1 cables for voice alarm systems complying with UNI 9795: 2013 EN 50200 PH 120

STANDARD USE: Signalling, control cables for fixed installation in crowded areas with danger of fire (theaters, banks, stores, shops, multi-storey buildings, schools, hotels, airports, hospitals, etc.)
SPECIAL FEATURES: Fire resistant low smoke, zero halogen, cables for category 1(1) systems suitable to be installed in a single duct, without interposition of separator, with power cables with operating voltage up to 0,6/1 KV.

 

Technical features

 

Conductors

Stranded bare copper conductors
CEI 20-29 cl.5, EN 60228, IEC 60228 ref.

 

Insulation

Glass/Mica tape and halogen free crosslinked compound CEI 20-11, EN 50363-0 quality E4. Colour code: Red, Black.

 

Jacket

Special flame retardant, halogen free, low smoke compound CEI 20-11, EN 50363-0 quality M1, VDE 0207 HM2. Colour: Violet Ral 4005.

 

Elettrical resistance

1 mm2: < 19,5 Ohm/Km
1,5 mm2: < 13,3 Ohm/Km
2,5 mm2: < 7,98 Ohm/Km
4 mm2: < 4,95 Ohm/Km
6 mm2: < 3,30 Ohm/Km 

Operating temperature

-25°C +90°C(posa fissa)
 

Bending radius

5 volte il diametro del cavo (posa fissa).
 

Operating voltage

100/100 V

Test voltage

2000 V
 

Fire resistance test

CEI 20-36/4-0 PH 30, CEI EN 50200 PH 30 (IMQ report 01SL00223/1)

Flame retardant test

CEI 20-35/1-2, EN 60332-1-2

Non-halogen verification

< 0,5 % (CEI 20-37/2-1, CEI EN 50267-2-1, IEC 60754-1)

Corrosivity of combustion gas

pH: > 4,3 - Conductivity: < 10 μS/mm
(CEI 20-37/2-2, CEI EN 50267-2-2, IEC 60754-2)

Smoke density

Transmission of light: > 70% (CEI 20-37/3-1, EN 61034-2)

Toxicity index

< 2 (CEI 20-37/4-0)