Categories


KNX/IEB PVC Cable CPR Eca
STANDARD USE
Cables for bus systems used in home & building automation for intelligent control of lighting, heating, air conditioning, entrance management
and energy management.
The KNX bus is used to connect different types of sensors (e.g. switches, thermostats, timers) and actuators (e.g. motors, heaters
and air conditioners, lamps, roller shutters).
Data sheet
More info
Technical details:

Conductors
Solid bare copperdiameter 0.80 mm
(nominal cross sect. area 0.50 mm2 - 20AWG)

Insulation
Special halogen free low smoke compound
Shield
Aluminium/polyester tape helically wound, solid bare copperdrain wire 0,80 mm diameter

Jacket
Polyvinylchloride (PVC) lead freColour: green

Electrical Conductor Resistance
< 37.5 Ohm/Km
Working Temperature
-15°C + 80°C
Working Voltage
50 V
Test Voltage
800 V
Surface Transfer Impedance
max 200 mohm/m (f<10MHz)
Capacitance
cond/cond: < 100 pF/m
Flame Retardant Test
Standard: CEI 20-35 (IEC 332.1) Ref.On request: CEI 20-22 II (IEC 332.3A) Ref

CPR
The Above Mentioned CablesCan Be Supplied With CPR Eca Euro Class certification
ARMATURA / ARMOURED | CODICE / CODE | FORMAZIONE / TYPE | Ø ESTERNO / OUTER Ø ±5% (mm) | PESO MEDIO / AVERAGE WEIGHT (kg/km) |
---|---|---|---|---|
NON ARMATO / UNARMOURED | 2x0,8 | 5,0 | ||
2x2x0,8 | 5,6 | |||
ARMATO / ARMOURED | 2x0,8 | 7,0 | ||
2x2x0,8 | 7,6 |